MARINESHELF publishes articles contributed by seafarers and other marine related sites solely for the benefit of seafarers .All copyright materials are owned by its respective authors or publishers.
Regulations
Regulations
Taken from SOLAS 1974
Regualtion II/2ARegulation
12 Automatic sprinkler, fire detection and fire alarm systems1.1 Any
required automatic sprinkler, fire detection and fire alarm system shall be
capable of immediate operation at all times and no action by the crew shall be
necessary to set it in operation. It shall be of the wet pipe type but small
exposed sections may be of the dry pipe type where in the opinion of the
Administration this is a necessary precaution. Any parts of the system which
may be subjected to freezing temperatures in service shall be suitably
protected against freezing. It shall be kept charged at the necessary pressure
and shall have provision for a continuous supply of water as required in this
regulation.1.2 Each
section of sprinklers shall include means for giving a visual and audible alarm
signal automatically at one or more indicating units whenever any sprinkler
comes into operation. Such alarm systems shall be such as to indicate if any
fault occurs in the system. Such units shall indicate in which section served
by the system fire has occurred and shall be centralized on the navigation
bridge and in addition, visible and audible alarms from the unit shall be
located in a position other than on the navigation bridge, so as to ensure that
the indication of fire is immediately received by the crew.2.1
Sprinklers shall be grouped into separate sections, each of which shall contain
not more than 200 sprinklers. In passenger ships any section of sprinklers
shall not serve more than two decks and shall not be situated in more than one
main vertical zone. However, the Administration may permit such a section of
sprinklers to serve more than two decks or be situated in more than one main
vertical zone, if it is satisfied that the protection of the ship against fire
will not thereby be reduced.2.2 Each
section of sprinklers shall be capable of being isolated by one stop valve
only. The stop valve in each section shall be readily accessible and its
location shall be clearly and permanently indicated. Means shall be provided to
prevent the operation of the stop valves by any unauthorized person.2.3 A
gauge indicating the pressure in the system shall be provided at each section
stop valve and at a central station.2.4 The
sprinklers shall be resistant to corrosion by marine atmosphere. In
accommodation and service spaces the sprinklers shall come into operation
within the temperature range from 68АC to 79АC, except that in locations such
as drying rooms, where high ambient temperatures might be expected, the
operating temperature may be increased by not more than 30АC above the maximum
deckhead temperature.2.5 A
list or plan shall be displayed at each indicating unit showing the spaces
covered and the location of the zone in respect of each section. Suitable
instructions for testing and maintenance shall be available.3
Sprinklers shall be placed in an overhead position and spaced in a suitable
pattern to maintain an average application rate of not less than 5 l/m2/min
over the nominal area covered by the sprinklers. However, the Administration
may permit the use of sprinklers providing such an alternative amount of water
suitably distributed as has been shown to the satisfaction of the
Administration to be not less effective.4.1 A
pressure tank having a volume equal to at least twice that of the charge of
water specified in this subparagraph shall be provided. The tank shall contain
a standing charge of fresh water, equivalent to the amount of water which would
be discharged in one minute by the pump referred to in paragraph 5.2, and the
arrangements shall provide for maintaining an air pressure in the tank such as
to ensure that where the standing charge of fresh water in the tank has been
used the pressure will be not less than the working pressure of the sprinkler,
plus the pressure exerted by a head of water measured from the bottom of the
tank to the highest sprinkler in the system. Suitable means of replenishing the
air under pressure and of replenishing the fresh water charge in the tank shall
be provided. A glass gauge shall be provided to indicate the correct level of
the water in the tank.4.2 Means
shall be provided to prevent the passage of seawater into the tank.5.1 An
independent power pump shall be provided solely for the purpose of continuing
automatically the discharge of water from the sprinklers. The pump shall be
brought into action automatically by the pressure drop in the system before the
standing fresh water charge in the pressure tank is completely exhausted.5.2 The
pump and the piping system shall be capable of maintaining the necessary
pressure at the level of the highest sprinkler to ensure a continuous output of
water sufficient for the simultaneous coverage of a minimum area of 280 m2 at
the application rate specified in paragraph 3.5.3 The
pump shall have fitted on the delivery side a test valve with a short
open-ended discharge pipe. The effective area through the valve and pipe shall
be adequate to permit the release of the required pump output while maintaining
the pressure in the system specified in paragraph 4.1.5.4 The
sea inlet to the pump shall wherever possible be in the space containing the
pump and shall be so arranged that when the ship is afloat it will not be
necessary to shut off the supply of seawater to the pump for any purpose other
than the inspection or repair of the pump.6 The
sprinkler pump and tank shall be situated in a position reasonably remote from
any machinery space of category A and shall not be situated in any space
required to be protected by the sprinkler system.7.1 In
passenger ships there shall be not less than two sources of power supply for
the seawater pump and automatic alarm and detection system. Where the sources
of power for the pump are electrical, these shall be a main generator and an
emergency source of power. One supply for the pump shall be taken from the main
switchboard, and one from the emergency switchboard by separate feeders
reserved solely for that purpose. The feeders shall be so arranged as to avoid
galleys, machinery spaces and other enclosed spaces of high fire risk except in
so far as it is necessary to reach the appropriate switchboards, and shall be
run to an automatic change-over switch situated near the sprinkler pump. This
switch shall permit the supply of power from the main switchboard so long as a
supply is available therefrom, and be so designed that upon failure of that
supply it will automatically change over to the supply from the emergency
switchboard. The switches on the main switchboard and the emergency switchboard
shall be clearly labelled and normally kept closed. No other switch shall be
permitted in the feeders concerned. One of the sources of power supply for the
alarm and detection system shall be an emergency source. Where one of the sources
of power for the pump is an internal combustion engine it shall, in addition to
complying with the provisions of paragraph 6, be so situated that a fire in any
protected space will not affect the air supply to the machinery.7.2 In
cargo ships there shall not be less than two sources of power supply for the
seawater pump and automatic alarm and detection system. If the pump is
electrically driven it shall be connected to the main source of electrical
power, which shall be capable of being supplied by at least two generators. The
feeders shall be so arranged as to avoid galleys, machinery spaces and other
enclosed spaces of high fire risk except in so far as it is necessary to reach
the appropriate switchboards. One of the sources of power supply for the alarm
and detection system shall be an emergency source. Where one of the sources of
power for the pump is an internal combustion engine it shall, in addition to
complying with the provisions of paragraph 6, be so situated that a fire in any
protected space will not affect the air supply to the machinery.8 The
sprinkler system shall have a connection from the ship's fire main by way of a
lockable screw-down non-return valve at the connection which will prevent a
backflow from the sprinkler system to the fire main.9.1 A
test valve shall be provided for testing the automatic alarm for each section of
sprinklers by a discharge of water equivalent to the operation of one
sprinkler. The test valve for each section shall be situated near the stop
valve for that section.9.2 Means
shall be provided for testing the automatic operation of the pump on reduction
of pressure in the system.9.3
Switches shall be provided at one of the indicating positions referred to in
paragraph 1.2 which will enable the alarm and the indicators for each section
of sprinklers to be tested.10 Spare
sprinkler heads shall be provided for each section of sprinklers to the
satisfaction of the Administration.
3 comments:
I got some valuable points through this blog.
Fixed Gas Detection Saudi Arabia
Thank you for your post, I look for such article along time, today i find it finally. If you're searching for Trusted and reputable Pump suppliers in India, then you can checkout here at @ TFTpumps.com, where we supply all kinds of Pumps to Industries.
Visit Fire sprinkler systems are a critical part of any building's safety system, as they provide the necessary water pressure to activate the sprinklers in the event of a fire.
Post a Comment