MARPOL 73/78 ANNEX VI SURVEY CHECK LIST (Provisional)
- From an external examination is the incinerator in a generally satisfactory condition & free from leaks of gases or smoke?
- Are the warning & instruction plates legible & secured in a prominent position?
- Is the manufacturers name , incinerator model number/type & capacity in heat units per hour permanently marked on the incinerator?
- Are the incinerators casing insulation arrangement in good condition?
- Are the following alarms & safety devices in operational?
a) Was it verified that the O2 content in the combustion chamber is between 6-12%? Flue gas high temperature alarms & shutdown.
b) Combustion temperature control & shutdown.
c) Combustion chamber negative pressure.
d) Flame safeguards control, alarms & shutdown.
e) All alarms both visual, audible & functioning & do they indicate the cause of failure.
f) Power loss alarm & auto shutdown arrangements.
g) Charging arrangement.
h) Low fuel oil pressure alarm / shutdown.
i) Emergency stop switch & electrical isolating arrangements.
j) Interlocks?
- Are complete instruction & maintenance manuals available on board?
- Is staff suitably trained?
- Are drip trays fitted under each burner, pump, and strainer & are they in good condition?
- Was the combustion chamber flue gas outlet temperature verified as between 850-1200 °C?